Jasper
Electronic
Compact
PCI Power Supply
200 Watt, DC Input
Model
# DPCI204-1022-4-M1000
FEATURES:
- STANDARD
PCI OUTPUT VOLTAGES: 5.0V, 3.3V, + 12.0V, WITH VARIABLE CURRENTS
- HOT
SWAP, N + 1 REDUNDANT WITH INTERNAL OR-ING DIODES
- .99
POWER FACTOR CORRECTED DC 40-70V
- CURRENT
SHARING ON 5.0V AND 3.3V OUTPUTS
- STANDARD
47 PIN OR 32 PIN DIN CONNECTOR CONFIGURATIONS
- COMPLIES WITH ALL REQUIREMENTS OF
PICMG POWER INTERFACE SPECIFICATIONS
Specifications:
-INPUT-
Voltage/Current
.............. DC 36-72, 7.9A
Fusing
............................ Internal line fuse provided, non-user
serviceable.
DC- 10.0A.
Inrush Current
................ Thermistor soft start.
Transient Protection
....... MOV. Withstands transients as specified by
IEEE C62.41 3KV (differential and common mode).
EMI Filtering
................... Meets IFCC Level B, and EN 55022 Level B
(conducted).
Efficiency........................
70% typical at full load.
Redundant/Hot Swap .....
Full power N+1 redundant, hot swap capable.
-OUTPUTS-
Model
|
V/A V1
|
V2
|
V3
|
V4
|
DPCI2043
|
5.0/33
|
3.3/33
|
+12/6.0
|
- 12/1.0
|
Line Regulation
.............. At the Sense Point, Over Full Input Range <±1%,
sense
leads connected.
Load Regulation
............. Output voltage droops with increasing load.
Minimum Loading...........
5% minimum on V1.
Stability
.......................... Output drift <±0.2% after 20
minute
warm-up.
Temp. Coefficient
........... <±0.02%/ºC, 0º - 50ºC, after 20
minute warm- up.
Dynamic Response ........Less than 3% deviation with
a 25%
load change
at 1A/µsec. Output returns to within 1% in less
than 300µsec.
Ripple and Noise
(PARD)...........................
For all outputs, 50mV max or 1% peak-to-peak
nominal,
which ever is greater, DC to 20MHz
bandwidth with a coaxial probe and
0.1µF/22µF
capacitors at the output terminals.
Current Sharing/
Parallel N+1 Operation ...
V1, V2, V3 Outputs. Droop method standard.
Optional single wire design in development.
Consult factory for availability.
Remote
Sense................ V1, V2, V3 outputs compensate for up to 0.25V
total line drop in the load cables. Outputs are
internally sensed if leads are opened.
Hold-Up Time
................. Outputs remain in regulation >15msec minimum
following loss of AC power at low line, full load.
Over Current/Short
Circuit
Protection............ Current limit on all outputs. Automatic recovery
when overload is removed.
Over Temperature
Protection.......................
Internal temperature sensing. Causes all outputs
to shut down. Automatic recovery.
Over/Under Shoot
.......... None at turn-on or turn-off.
Under Voltage Warning
..Any output dropping below 10% of nominal
triggers the power fail warning signal.
Over Voltage
Protection
.......................Non-crowbar type. Any output that exceeds
25%
±10% of
nominal Vout will cause all outputs
to latch off. Remote inhibit, enable or input
recycle required to reset.
-SIGNALS, INDICATORS and
CONTROLS-
Remote
Enable...............Enabled by closed circuit or TTL logic 0.
Disabled by open circuit or TTL logic 1.
Power Fail Warning
.......Loss of input AC causes a TTL compatible signal to go low
>4msec prior to any output dropping out of regulation. At AC
turn-on, signal stays low until all outputs are in regulation. PF
signal also triggered by an under voltage condition on any output.
LED
Indicator..................Dual LEDs. Green indicates input power ON
and outputs within regulation. Off or Amber indicates
input and/or output power fault.
-OPERATING ENVIRONMENT-
Operating Temperature
..0º
– 50ºC ambient at full load, with specified airflow.
Cooling
...........................A minimum of 15 cfm / 400 lfm direct forward
airflow required to achieve full rated power and specified MTBF.
Consult factory for derating guidelines with reduced or reversed
airflow.
Relative
Humidity............Up to 90% RH, non-condensing.
Operational Vibration
......0.75G peak, 5 – 500Hz along three orthogonal axis.
Storage
Temperature......-40º to 85ºC.
Altitude
...........................Operating to 10,000 ft; Storage to 30,000 ft.
MTBF
.............................Designed for 150,000 hrs at 25ºC.
-INTERCONNECT-
I/O
Connectors. Refer to JE Outline
Configuration Drawing #02102-000 or the chart in this catalog for pin
function identification-
47 Circuit
....................Positronic Ind. P/N PCIH47M400A1.
Mates with PI P/N PCIH47F300A1.
32 Circuit (AC
only).....Contact factory.
Note: Use of the specified
mating connector is required to insure proper "make/break" sequential
contact sequence.
-MECHANICAL-
Outline............................3U
x 8HP front panel. Refer to JE Outline Dwg #02102-000 or the Mechanical
Outline in this catalog. Complies with all current PICMG ® CompactPCI PSU
specifications.
Retaining
Latches...........Supplied with a single Rittal #3686.135 Type VII
(Telecom) Lower Latch. Other manufacturers and types available. Consult
factory.
Guide
Rails.....................Supplied with .260[6.61] offset guide rails
for use with Rittal 3687.832 (or equivalent) PSU guides.
Front Panel
Overlay........Supplied with Lexan overlay and JE Logo. May be deleted,
or supplied with customer specified logo or other information. Consult
factory.
Weight
............................Approx: 1.8 lbs / 1.06 kgs.
-SAFETY-
All
Models....................... Recognized to U.S. and Canadian
Bi-National Standard CSA C22.2 No. 60950 / UL 60950, Third (3 rd ) Edition (cULus);
TUV
approved to TUV EN60950/A1-A4/A11. CE Marked. CB
Reports available on request.
1 Total loading on all
outputs not to exceed 175W.
Combined load on V1 + V2
not to exceed 30A.
(DPCI174 DC input model
output ratings identical to AC version.)
2 Total loading on all
outputs not to exceed 200W.
Combined load on V1 + V2
not to exceed 38A.
3 Total loading on all
outputs not to exceed 200W.
Combined load on V1 + V2
not to exceed 38A.
|