Specifications:

GENERAL INFORMATION

Manufacturer

POWERCOM

Model Type

KING RM

Model Name

KIM-1000APRM

AC INPUT

AC Input Capacity on Battery

1000VA

AC Input Voltage

(+/-) 25% at line input

AC Input Frequency

50 or 60 Hz+/-5Hz (auto sensing)

AC Input Phase

Single

AC OUTPUT

AC Output Voltage

Simulated sine ware at 100V/110V/115V/120V/220V/230V/240V +/-5%

AC Output Frequency

50 or 60 Hz +/- 0.5%

AC Output Voltage Regulation

AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal

AC Output Transfer

2/4 milliseconds, including detection time

PROTECTION

Protection Spike

320 Joules, 2ms

Protection EMI/RFI

10dB at 0.15 MHz, 50 dB at 30 MHz

Protection Overload

UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec

Protection Unit

Fuse for overload & short circuit protection

Protection 10 BaseT

Network (UTP, RJ-45) compatible jacks

Protection Short Protection

UPS output cut off immediately or input fuse protection

BATTERY

Battery Type

Sealed, Maintenance-free lead acid.

Battery Typical

8 hours (to 90% of full capacity)

Battery Protection

Automatic self-test & discharge protection, replace battery indicator

Battery Run Time

50 - 60 minutes

PHYSICAL

Physical Weight kgs

10.5

Physical Weight lbs

(23.1lb)

Physical Shipping Weight kgs

11.7

Physical Shipping Weight lbs

(25.7lb)

Physical Dimension mm

483x362x44(1U)

INDICATOR

LED

LED

ALARM

Alarm Battery Backup

Slow beeping sound (about 0.47 Hz)

Alarm Battery Low

Rapid beeping sound (about 1.82Hz)

Alarm Overload

Continue beeping sound

INTERFACE

Interface RS-232

RS-232C Bi-directional communication port

ENVIRONMENT

Environment Ambient

3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c

Environment Audible

<40dBA (1 meter from surface)

Environment Storage Condition

15,000 meters max. elevation


ORDERING INFORMATION
Call us for more details and quote.