Power Com
Uninterruptible Power System (UPS)
Model # KIN-1000APRM
Rack Mount, 120 Volts Input
|
Specifications:
|
GENERAL
INFORMATION
|
Manufacturer
|
POWERCOM
|
Model Type
|
KING RM
|
Model Name
|
KIM-1000APRM
|
|
AC
INPUT
|
AC Input Capacity on
Battery
|
1000VA
|
AC Input Voltage
|
(+/-) 25% at line input
|
AC Input Frequency
|
50 or 60 Hz+/-5Hz (auto
sensing)
|
AC Input Phase
|
Single
|
|
AC
OUTPUT
|
AC Output Voltage
|
Simulated sine ware at
100V/110V/115V/120V/220V/230V/240V +/-5%
|
AC Output Frequency
|
50 or 60 Hz +/- 0.5%
|
AC Output Voltage
Regulation
|
AVR automatically increase
output voltage 15% above input voltage if -9% to -25% of nominal. AVR
decrease output voltage 13% below input voltage if +9% to +25% of
nominal
|
AC Output Transfer
|
2/4 milliseconds,
including detection time
|
|
PROTECTION
|
Protection Spike
|
320 Joules, 2ms
|
Protection EMI/RFI
|
10dB at 0.15 MHz, 50 dB at
30 MHz
|
Protection Overload
|
UPS automatic shutdown if
overload exceeds 110% nominal at 60 sec and 130% at 3 sec
|
Protection Unit
|
Fuse for overload &
short circuit protection
|
Protection 10 BaseT
|
Network (UTP, RJ-45)
compatible jacks
|
Protection Short Protection
|
UPS output cut off
immediately or input fuse protection
|
|
BATTERY
|
Battery Type
|
Sealed, Maintenance-free
lead acid.
|
Battery Typical
|
8 hours (to 90% of full
capacity)
|
Battery Protection
|
Automatic self-test &
discharge protection, replace battery indicator
|
Battery Run Time
|
50 - 60 minutes
|
|
PHYSICAL
|
Physical Weight kgs
|
10.5
|
Physical Weight lbs
|
(23.1lb)
|
Physical Shipping Weight
kgs
|
11.7
|
Physical Shipping Weight
lbs
|
(25.7lb)
|
Physical Dimension mm
|
483x362x44(1U)
|
|
|
ALARM
|
Alarm Battery Backup
|
Slow beeping sound (about
0.47 Hz)
|
Alarm Battery Low
|
Rapid beeping sound (about
1.82Hz)
|
Alarm Overload
|
Continue beeping sound
|
|
INTERFACE
|
Interface RS-232
|
RS-232C Bi-directional
communication port
|
|
ENVIRONMENT
|
Environment Ambient
|
3,500 meters max.
elevation, 0-95% humidity non-condensing, 0-40 deg c
|
Environment Audible
|
<40dBA (1 meter from
surface)
|
Environment Storage
Condition
|
15,000 meters max.
elevation
|
|