Specifications:
|
GENERAL
INFORMATION
|
Manufacturer
|
POWERCOM
|
Model Type
|
SMART KING RM
|
Model Name
|
SMK-2000A-RM
|
|
AC
INPUT
|
AC Input Capacity on
Battery
|
2000VA
|
AC Input Voltage
|
(+/-) 25% at line input
|
AC Input Frequency
|
50 or 60 Hz+/-5Hz (auto
sensing)
|
AC Input Phase
|
Single
|
|
AC
OUTPUT
|
AC Output Voltage
|
Pure sine wave at +/-5% of
nominal, -10% of nominal after low battery warning
|
AC Output Frequency
|
50 or 60 Hz +/- 0.5%
|
AC Output Voltage
Regulation
|
AVR automatically increase
output voltage 15% above input voltage if -9% to -25% of nominal. AVR
decrease output voltage 15% below input voltage if +9% to +25% of
nominal
|
|
PROTECTION
|
Protection Spike
|
320 Joules, 2ms
|
Protection EMI/RFI
|
10dB at 0.15 MHz, 50 dB at
30 MHz
|
Protection Overload
|
UPS automatic shutdown if
overload exceeds 110% nominal at 20 sec and 125% at 5 sec
|
Protection Unit
|
Fuse for 110V models
(600VA~2500VA) and 220V models (under 1250VA), breaker for 110V model
(3000VA) and 220V models (above 1500VA)
|
Protection Transfer Time
|
2/4 milliseconds
(typical), including detection time
|
Protection Short Protection
|
UPS output cut off
immediately or input fuse( or breaker) protection
|
|
BATTERY
|
Battery Type
|
Hot swappable, sealed,
maintenance-free lead acid.
|
Battery Typical
|
4 hours (to 90% of full
capacity)
|
Battery Protection
|
Automatic self-test &
discharge protection, replace battery indicator
|
Battery Run Time
|
120 minutes
|
|
PHYSICAL
|
Physical Weight kgs
|
28.4
|
Physical Weight lbs
|
(62.5lb)
|
Physical Dimension mm
|
483x381x130
|
Physical Dimension inch
|
(19.0x15.0x5.2)
|
|
INDICATOR
|
LCD Indicators Status
|
Indicate line, bypass,
inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P
voltage, O/P frequency, inside temperature, fault status, load
|
|
ALARM
|
Alarm Battery Backup
|
Slow beeping sound (about
0.25 Hz)
|
Alarm Battery Low
|
Rapid beeping sound (about
1.00Hz)
|
Alarm Overload
|
Continue beeping sound
|
|
INTERFACE
|
Interface Dry Contact
|
Sends AC fail and battery
low signals, and receives shutdown signal from computer
|
Interface RS-232
|
Detect battery low,
Schedule UPS on/off, AC input/output power status display
|
Interface Option
|
Novell, SNMP, Windows NT,
Window 95/98/2000/ME/XP
|
|
ENVIRONMENT
|
Environment Ambient
|
3,500 meters max.
elevation, 0-95% humidity non-condensing, 0-48 deg c
|
Environment Audible
|
<40dBA (1 meter from
surface)
|
Environment Storage
Condition
|
15,000 meters max.
elevation
|
|
|
|
 |
 |
ORDERING INFORMATION |
 |
Call us for more details