High Availability Computing Solutions - Take a Look
|
|
|
|
|
          

 
 

Power Com
Uninterruptible Power System (UPS)
Model # SMK 2000A RM
 Rack Mount
115 Volts Input, Pure Sine Wave Output

Specifications:

GENERAL INFORMATION

Manufacturer

POWERCOM

Model Type

SMART KING RM

Model Name

SMK-2000A-RM

AC INPUT

AC Input Capacity on Battery

2000VA

AC Input Voltage

(+/-) 25% at line input

AC Input Frequency

50 or 60 Hz+/-5Hz (auto sensing)

AC Input Phase

Single

AC OUTPUT

AC Output Voltage

Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning

AC Output Frequency

50 or 60 Hz +/- 0.5%

AC Output Voltage Regulation

AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal

PROTECTION

Protection Spike

320 Joules, 2ms

Protection EMI/RFI

10dB at 0.15 MHz, 50 dB at 30 MHz

Protection Overload

UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec

Protection Unit

Fuse for 110V models (600VA~2500VA) and 220V models (under 1250VA), breaker for 110V model (3000VA) and 220V models (above 1500VA)

Protection Transfer Time

2/4 milliseconds (typical), including detection time

Protection Short Protection

UPS output cut off immediately or input fuse( or breaker) protection

BATTERY

Battery Type

Hot swappable, sealed, maintenance-free lead acid.

Battery Typical

4 hours (to 90% of full capacity)

Battery Protection

Automatic self-test & discharge protection, replace battery indicator

Battery Run Time

120 minutes

PHYSICAL

Physical Weight kgs

28.4

Physical Weight lbs

(62.5lb)

Physical Dimension mm

483x381x130

Physical Dimension inch

(19.0x15.0x5.2)

INDICATOR

LCD Indicators Status

Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status, load

ALARM

Alarm Battery Backup

Slow beeping sound (about 0.25 Hz)

Alarm Battery Low

Rapid beeping sound (about 1.00Hz)

Alarm Overload

Continue beeping sound

INTERFACE

Interface Dry Contact

Sends AC fail and battery low signals, and receives shutdown signal from computer

Interface RS-232

Detect battery low, Schedule UPS on/off, AC input/output power status display

Interface Option

Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP

ENVIRONMENT

Environment Ambient

3,500 meters max. elevation, 0-95% humidity non-condensing, 0-48 deg c

Environment Audible

<40dBA (1 meter from surface)

Environment Storage Condition

15,000 meters max. elevation


ORDERING INFORMATION
Call us for more details and quote.
   Return to Top | Terms & Conditions | Contact Us | Site Map | Company Info | © IBUS Corp. -2007 |